Portable Chiller Systems for Low Temperature Cooling

Process-Chiller, Water CooledLow Temperature Fluid Chillers

Thermonics portable chillers are a family of highly reliable, process chillers for low and ultra-low temperature, process cooling. These chillers are compatible with a variety of heat transfer fluids, providing high capacity cooling for demanding applications in industries such as automotive, energy, chemical processing, industrial, and semiconductor.

The chiller systems are equipped with a touch screen controller featuring remote communications, real-time graphing, and system diagnostics to monitor chiller health and prevent down-time.

In-house capabilities including thermodynamic, mechanical, electrical, and software disciplines with on-site chiller manufacturing to ensure that your total chiller system will perform to specifications.

Available in both Water-cooled and Air-cooled configurations.

 

Water Cooled Chillers

ModelTemperature
Range (°C)
Stability
(°C)
Cooling Capacity (kW @ 20°C Water Supply)Pump
Capacity
(GPM/LPM)
250-20-40-45-60-70-80
W-40-1100 -40 to +50 ±0.5 8.0 8.0 4.6 1.1 0.6       4 (15)
W-40-2000 -40 to +50 ±0.5 10.0 10.0 6.0 2.0 1.0       6 (23)
W-40-3100 -40 to +50 ±0.5 15.5 15.5 10.0 3.1 1.4       10 (38)
W-60-2800 -60 to +50 ±0.5 4.0 4.0 3.7 3.2 3.1 2.8     2.8 (11)
W-60-3100 -60 to +50 ±0.5 4.7 4.7 4.3 3.7 3.6 3.1 1.1   6 (23)
W-60-4700 -60 to +50 ±0.5 6.8 6.8 6.2 5.4 5.2 4.7 4.0   8 (30)
W-80-600 -80 to +50 ±0.5 2.5 2.5 2.3 2.1 2.0 1.8 1.6 0.6 2.8 (11)
W- 80-1800 -80 to +50 ±0.5 3.5 3.5 3.2 2.9 2.8 2.4 2.2 1.8 6 (23)
W-80-2500 -80 to +50 ±0.5 5.1 5.1 4.5 4.0 3.9 3.4 3.2 2.5 8 (30)

Air Cooled Chillers

ModelTemperature
Range (°C)
Stability
(°C)
Cooling Capacity (kW @ 25°C Ambient)Pump
Capacity
(GPM/LPM)
250-20-40-45-60-70-80
A-40-1100 -40 to +50 ±0.5 6.6 6.6 4.0 1.1 0.5       4 (15)
A-40-1900 -40 to +50 ±0.5 9.5 9.5 5.4 1.9 0.7       6 (23)
A-40-2700 -40 to +50 ±0.5 14.5 14.5 9.6 2.7 1.2       10 (38)
A-60-2700 -60 to +50 ±0.5 3.9 3.9 3.6 3.1 3.0 2.7     2.8 (11)
A-60-3000 -60 to +50 ±0.5 4.6 4.6 3.7 3.5 3.4 3.0     6 (23)
A-60-4600 -60 to +50 ±0.5 6.7 6.7 6.1 5.3 5.1 4.6     8 (30)
A-80-500 -80 to +50 ±0.5 2.3 2.3 2.2 2.1 2.0 1.8 1.5 0.5 2.8 (11)
A- 80-1700 -80 to +50 ±0.5 3.4 3.5 3.1 2.8 2.7 2.3 2.1 1.7 6 (23)
A-80-2400 -80 to +50 ±0.5 5.0 5.1 4.5 3.9 3.8 3.3 3.1 2.4 8 (30)

Notes:
1) Fluid pressure for all water-cooled and air-cooled models is 50 PSIG or less.
2) -40 and -60°C performance achieved with Syltherm XLT fluid. -80°C performance achieved with HFE-7100 fluid.
3) Consult factory for applications using other heat transfer fluids and flow rates.